Pluggable modular multi-pole DC SPD type 2 lightning current surge arrester for use in photovoltaic systems
Product Description
Pluggable modular multi-pole DC SPD type 2 lightning current surge arrester for use in photovoltaic systems
- With remote signaling contact for monitoring device (floating changeover contact) (S)
- For installation in the DC circuits of solar photovoltaic systems, string box, inverter
- Mode of Protection: (DC+) – PE, (DC-) – PE, (DC+) – (DC-)
- EU Category: Type 2
- Protective Elements: High Energy MOV
Technical data
Type | SLP40-DC75/2 | SLP40-DC75/2S |
SPD according to EN 61643-11 / IEC 61643-11 | type 2 / class II | type 2 / class II |
Nominal d.c. voltage Un | 48 V | 48 V |
Max. continuous operating d.c. voltage Uc | 75 V | 75 V |
Nominal discharge current (8/20μs) In | 20 kA | 20 kA |
Maximum discharge current (8/20μs) Imax | 40 kA | 40 kA |
Voltage Protection level UP | 0,3 kV | 0,3 kV |
Residual current – Leakage current at Uc [IPE] | < 0.1 mA | < 0.1 mA |
Max. Load current if connection series IL | 20 A | 20 A |
Response time tA | 25 ns | 25 ns |
Range of operating temperatures (TU) | -40/+80°C | -40/+80°C |
Operating state / fault indication | green / red | green / red |
Number of ports | 1 | 1 |
Cross-sectional area (min.) | 1.5 mm2 solid /flexible | 1.5 mm2 solid /flexible |
Cross-sectional area (max.) | 35 mm2 stranded / 25 mm2 flexible | 35 mm2 stranded / 25 mm2 flexible |
For mounting on | 35 mm DIN rail acc. to EN 60715 | 35 mm DIN rail acc. to EN 60715 |
Enclosure material | thermoplastic | thermoplastic |
Place of installation | indoor installation | indoor installation |
Degree of protection | IP 20 | IP 20 |
Capacity | 2 module(s), DIN 43880 | 2 module(s), DIN 43880 |
Approvals | – | – |
Type of remote signalling contact | – | changeover contact |
a.c. switching capacity | – | 250 V / 0.5 A |
d.c. switching capacity | – | 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
Cross-sectional area for remote signalling terminals | – | max. 1.5 mm2 solid / flexible |